• the earth resistance from 0.05 to 1500ω can be measured without the auxiliary earth spikes.
(the multiple earthing system.) 
• true rms
accurate true rms readings of ac current including distorted waveform from 1ma to 30.0a 
• noise check function 
a function to detect current, which effects on an earth resistance measurement and display ''noise'' mark on the lcd. 
• memory function 
save and display up to 100 measurement data. 
• data hold function / buzzer function / back light function 
• compliant with safety standards of iec 61010-1 : cat iv 300v pollution degree2 

note:
a single earthing can not be measured. (only for multiple earthing system)
  • true rms
  • φ32
  • backlight

earth resistance auto range 20.00/200.0/1500ω
±1.5%±0.05ω(0.00 - 20.99ω)*
±2%±0.5ω(16.0 - 99.9ω)
±3%±2ω(100.0 - 209.9ω)
±5%±5ω(160 - 399ω)
±10%±10ω(400 - 599ω)
ac current (50hz/60hz) auto range values are displayed, but accuracy isn't guaranted(600 - 1580ω)
100.0/1000ma/10.00/30.0a
±2%±0.7ma(0.0 - 104.9ma)
±2%(80ma - 31.5a)
operating indication earth resistance function : 
constant voltage injection
current detection (frequency : approx.2400hz)
dual integration
ac current function : successive approximation
over-range indication ''ol''is displayed when input exceeds the upper limit of a 卡塔尔世界杯中国足球赛事 range
response time approx. 7 seconds (earth resistance)
approx. 2 seconds (ac current)
sample rate approx. 1 times per second
current consumption approx. 50ma (max.100ma)
measurement time approx.12 hours (when r6 is used)
approx.24 hours (when lr6 is used)
auto power-off turns power off about 10 minutes after the last button operation.
conductor size approx. ø32mm
applicable standards iec 61010-1 cat Ⅳ 300v pollution degree2
iec 61010-2-032, iec 61326 (emc)
power source dc6v : r6(sizeaa manganese battery) x 4
or lr6 (sizeaa alkaline battery) x 4
dimensions 246(l)×120(w)×54(d)mm
weight approx. 780g (including batteries)
included accessories r6 x 4, instruction manual
8304 (resister for operation check)
9166 (carrying case[hard])